SPECIFICATIONS:
Power Line
Voltage: 110/220VAC, 50/60Hz
Power Consumption: 15VA maximum
Input Thermocouple (T/C): Type J, K, T,
R, B, S,
RTD: PT100 ohm RTD (385curve)
Linear: 4-20mA, 1-5VDC, 0-5VDC
Range: Per table in manual
Common Mode Rejection: > 120dB at 60Hz
Cold Junction Accuracy: ±0.2ºC
@ 25ºC
Ambient Error: ±0.01% span /ºC
from 25ºC ambient
Isolation inputs share common ground on
2 pen units
Input Impedance: Linear = 249 ohm/ TC =
470K ohm
Recording Chart Size: 10
Recording Accuracy: ± 0.5% of span
(100division span)
Sensor Break: Full scale Pen <10 seconds
Chart Speed: Configurable
Input Filtering: Programmable up to 120
seconds
Process Display Option Red LED , 4 digit,
.0,40
Options Relay: DPDT , 1.0Amps @ 120VAC resistive
Relay
Program: Process, Band, Non-latching, Latching
Error Protection: De-energized during sensor
break.
Hysteresis: Set at 2units, activation is
safe sided
Battery Back up: Ink Style: Up to 48hours
of recording (optional)
Thermal print style: Maintains real time
clock only
Environmental and Physical Operating Temperature:
0 to 60ºC
Storage Temperature: -40 to 65ºCHumidity:0-90%
RH (non-condensing)
Vibration: 0.3 to 100 Hz @ 0.2 g
Mounting: ±20degrees of vertical
± 10 degrees of horizontal
Mouldings: Fire retardant Noryl w/acrylic
window
Panel Rating: Nema 3 std (Nema 4 option)
Dimensions: 14.0 (H) x 14.0 (W) x 3.8 (D)
7 pounds maximum